PHOENIX CONTACT Power supply unit - QUINT4-PS/1AC/24DC/40 2904603 input: 1-phase, output: 24 V DC/40 A.
Input Data
Control input (configurable) Rem Output power ON/OFF (SLEEP MODE)
Default Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
AC operation
Network type Star network
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Electric strength, max. 300 V AC 60 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current typ. 12 A (at 25 °C)
Inrush current integral (I2t) < 1 A2s
Inrush current limitation 12 A (after 1 ms)
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
16.7 Hz (acc. to EN 50163)
Mains buffering time typ. 29 ms (120 V AC)
typ. 32 ms (230 V AC)
Current consumption 13.6 A (100 V AC)
10 A (120 V AC)
5.2 A (230 V AC)
5.4 A (240 V AC)
Input fuse 16 A (slow-blow, internal)
Recommended breaker for input protection 16 A ... 20 A (Characteristic B, C, D, K or comparable)
Discharge current to PE < 3.5 mA 1.7 mA (264 V AC, 60 Hz) DC operation Nominal input voltage range 110 V DC ... 250 V DC Input voltage range 110 V DC ... 250 V DC -18 % ... +40 % Voltage type of supply voltage DC Current consumption 12 A (110 V DC) 5 A (250 V DC) Output Data Efficiency typ. 94.8 % (120 V AC) typ. 95.9 % (230 V AC) Nominal output voltage 24 V DC Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (constant capacity) Nominal output current (IN) 40 A Static Boost (IStat.Boost) 45 A Dynamic Boost (IDyn.Boost) 60 A (5 s) Selective Fuse Breaking (ISFB) 215 A (15 ms) Magnetic circuit breaker tripping A1...A40 / B2...B25 / C1...C13 / Z1...Z16 Derating > 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 1 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Short-circuit-proof yes
Signal
No-load proof yes
Output power 960 W
1080 W
1440 W
Maximum no-load power dissipation < 4 W (120 V AC)
< 4 W (230 V AC)
Power loss nominal load max. < 50 W (120 V AC)
< 50 W (230 V AC)
Power dissipation SLEEP MODE < 3 W (120 V AC)
< 3 W (230 V AC) Crest factor typ. 1.5 (120 V AC) typ. 1,6 (230 V AC) Connection in parallel yes, for redundancy and increased capacity Connection in series yes Signal Signal ground SGnd Reference potential for Out1, Out2, and Rem Signal Out 1 (configurable) Digital 24 V DC 20 mA Default 24 V DC 20 mA 24 V DC for UOut > 0.9 x USet
Signal Out 2 (configurable)
Digital 24 V DC 20 mA
Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Default 24 V DC 20 mA 24 V DC for POut < PN Signal relay 13/14 (configurable) Default closed (Uout > 0.9 USet)
Digital 24 V DC 1 A
30 V AC/DC 0.5 A
Commercial Data
Item number 2904603
Packing unit 1 pc
Minimum order quantity 1 pc
Product Key CMPI13
Catalog Page Page 235 (C-4-2019)
GTIN 4055626355092
Weight per Piece (including packing) 3,250 g
Weight per Piece (excluding packing) 2,887 g
Customs tariff number 85044083
Country of origin TH