Pepperl+Fuches KFD2-UFT-Ex2.D Frequency Converter with Direction and Synchronization Monitor, 2-channel isolated barrier.
This isolated barrier is used for intrinsic safety applications. It analyzes 2 digital signals (NAMUR sensor/mechanical contact) from a hazardous area and functions as a rotation direction indicator, slip monitor, frequency monitor or synchronization monitor.
Each proximity sensor or switch controls a passive transistor output. The 2 relay outputs indicate if the input signal is above or below the trip value or the rotational direction.
The analog output can be programmed to be proportional to the input frequency or slip differential.
The unit is easily programmed by the use of a keypad located on the front of the unit or with the PACTware⢠configuration software.
Line fault detection of the field current is indicated by a red LED.
Technical Data
General specifications
Signal type Digital Input
Supply
Connection terminals 23+, 24- or power feed module/Power Rail
Rated voltage Ur 20 ... 30 V DC
Rated current Ir approx. 130 mA
Power dissipation 2.2 W
Power consumption 2.5 W
Interface
Programming interface programming socket
Input
Connection side field side
Connection input I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Pulse duration min. 250 µs , overlap on direction of rotation signal: ℠125 µs
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Line fault detection breakage I ⤠0.15 mA; short-circuit I > 6.5 mA
Input III, IV
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA Open circuit voltage/short-circuit current 18 V / 5 mA Output Connection side control side Connection output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 19+, 20- output IV: terminals 21+, 20- output V: terminals 7-, 8+ Output I, II signal , relay Contact loading 253 V AC / 2 A / cos Ļ ā„ 0.7 ; 40 V DC / 2 A Mechanical life 5 x 107 switching cycles Energized/De-energized delay approx. 20 ms / approx. 20 ms Output III and IV signal , electronic output, passive Contact loading 40 V DC Signal level 1-signal: (external voltage) - 2.5 V max. for 10 mA or 3 V max. for 100 mA (100 mA, short-circuit proof) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: switched off (off-state current ⤠10 µA) Output V analog Current range 0 ... 20 mA or 4 ... 20 mA Open loop voltage max. 24 V DC Load max. 650 Ī© Fault signal downscale I ⤠3.6 mA, upscale I ā„ 21.5 mA (acc. NAMUR NE43) Collective error message Power Rail Transfer characteristics Input I and II Measurement range 0.001 ... 1000 Hz Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Measuring time frequency measurement: < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay ⤠200 ms
Output V
Resolution < 10 µA
Accuracy < 30 µA Influence of ambient temperature 0.005 %/K (50 ppm) Galvanic isolation Input I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff Input III, IV/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff Output III, IV/power supply and collective error basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff Output III, IV/input III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff Output III, IV/V basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff Output V/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff Interface/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff Interface/output III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff Indicators/settings Display elements LEDs , display Control elements Control panel Configuration via operating buttons via PACTware Labeling space for labeling at the front Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 (industrial locations) Low voltage Directive 2014/35/EU EN 61010-1:2010 Conformity Electromagnetic compatibility NE 21:2006 Degree of protection IEC 60529:2001 Input EN 60947-5-6:2000 Ambient conditions Ambient temperature -20 ... 60 °C (-4 ... 140 °F) Mechanical specifications Degree of protection IP20 Connection screw terminals Mass 300 g Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001 Data for application in connection with hazardous areas EU-type examination certificate TĆV 99 ATEX 1471 Marking 1 II (1)G [Ex ia Ga] IIC 1 II (1)D [Ex ia Da] IIIC 1 I (M1) [Ex ia Ma] I Supply Maximum safe voltage Um 40 V DC (Attention! Um is no rated voltage.) Input I and II terminals 1+, 3-; 4+, 6-: Ex ia Voltage Uo 10.1 V Current Io 13.5 mA Power Po 34 mW (linear characteristic) Input III and IV terminals 13+, 14-; 15+, 14- non-intrinsically safe Maximum safe voltage Um 40 V (Attention! Um is no rated voltage.) Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe Maximum safe voltage Um 253 V (Attention! The rated voltage can be lower.) Contact loading 253 V AC/2 A/cos Ļ > 0.7; 40 V DC/2 A resistive load
Output III and IV terminals 19, 20, 21 non-intrinsically safe
Maximum safe voltage Um Um 40 V DC (Attention! Um is no rated voltage.)
Output V terminals 8+, 7- non-intrinsically safe
Maximum safe voltage Um Um 40 V DC (Attention! Um is no rated voltage.)
Interface RS 232
Maximum safe voltage Um 40 V (Attention! Um is no rated voltage.)
Certificate TĆV 02 ATEX 1885 X