Pepperl+Fuches KFD0-SD2-Ex1.1180 Solenoid Driver, 1-channel isolated barrier, 24 V DC supply (loop powered), current limit 80 mA at 11 V DC.
This isolated barrier is used for intrinsic safety applications. It supplies power to solenoids, LEDs, and audible alarms located in a hazardous area.
It is loop powered, so the available energy at the output is received from the input signal. The output signal has a resistive characteristic. As a result the output voltage and current are dependent on the load and the input voltage.
At full load, 11 V at 80 mA is available for the hazardous area application.
Technical Data
General specifications
Signal type Digital Output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3
Supply
Rated voltage Ur
loop powered
Power dissipation < 1 W (⤠30 V)
Input
Connection side control side
Connection terminals 7, 8
Rated voltage Ur 20 ... 35 V DC
Current 140 mA at 20 V input voltage, load = 140 Ī©
100 mA at 35 V input voltage, load = 140 Ī©
Output
Connection side field side
Connection terminals 1+, 2-
Internal resistor Ri ⤠150 Ω
Current Ie ā„ 80 mA
Voltage Ue ā„ 11 V
Open loop voltage Us min. 22.7 V
Output rated operating current 80 mA
Output signal These values are valid for the rated operating voltage 20 ... 35 V DC.
Energized/De-energized delay single operation: typ. 1.7 ms/50 µs; periodical: typ. 5 µs/50 µs
Indicators/settings
Display elements LED
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2004
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BASEEFA 06 ATEX 0252
Marking 1 II (1)G [Ex ia Ga] IIB, II (1)D [Ex ia Da] IIIB, I (M1) [Ex ia Ma] I (-20 °C ⤠Tamb ⤠60 °C)
Voltage Uo 25.2 V
Current Io 184 mA
Power Po 1159 mW
Input
Maximum safe voltage Um 250 V (Attention! The rated voltage can be lower.)
Certificate TĆV 99 ATEX 1499 X
Marking 1 II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0309
UL approval
Control drawing 116-0316 (cULus)
IECEx approval
IECEx certificate IECEx BAS 06.0058
IECEx CML 19.0093X
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc