MTL4521/L – MTL5521 SOLENOID/ ALARM DRIVER loop-powered, IIC
The MTLx521 and the MTL4521L are loop-powered modules which enable a device located in the hazardous area to be controlled from the
safe area. They can all drive a certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED.
SPECIFICATION
Number of channels
One
Location of load
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Input voltage
20 to 35V dc
Hazardous-area output (MTLx521)
Minimum output voltage: 13.6V at 48mA
Maximum output voltage: 24V from 180Ω
Current limit: 48mA minimum
Hazardous-area output (MTL4521L)
Minimum output voltage: 11.1V at 48mA
Maximum output voltage: 24V from 232Ω
Current limit: 48mA minimum
Output ripple
< 0.5% of maximum output, peak to peak
Response time
Output within 10% of final value within 100ms
LED indicator
Yellow: output status, on when output active
Maximum current consumption
90mA at 24V
Power dissipation within unit
1.4W at 24V
Safety description (MTLx521)
Uo=25V Io=147mA Po=0.92W Um = 253V rms or dc
Safety description (MTL4521L)
Uo= 25V Io= 108mA Po= 0.68W Um = 253V rms or dc
MTL4501-SR
MTL5501-SR
MTL4504
MTL4510
MTL4510B
MTL4511
MTL4513
MTL4514D
MTL4514N
MTL4514_B
MTL4516
MTL4516C
MTL4517
MTL4521
MTL4521L
MTL4523
MTL4523L
MTL4523R
MTL4523V-VL
MTL4524
MTL4524S
MTL4525
MTL4526
MTL4541
MTL4541A
MTL4541AS
MTL4541B
MTL4541P
MTL4541S
MTL4541T
MTL4544
MTL4544A
MTL4544AS
MTL4544B
MTL4544D
MTL4544S
MTL4546
MTL4546C
MTL4546S
MTL4546Y
MTL4549
MTL4549C
MTL4549Y
MTL4573
MTL4575
MTL4576-RTD
MTL4576-THC
MTL4581
MTL4582B
MTL4531
MTL4532
MTL4561
MTL4599
MTL4599N
Reviews